Common Air Conditioning Refrigerant Leakage Several Major Parts And Treatment Methods

- Feb 01, 2019-

Common Air Conditioning Refrigerant Leakage Several Major Parts and Treatment Methods


The air conditioning and refrigeration pipeline system mainly consists of a compressor, a condenser, a throttle valve, an evaporator and a connecting copper pipe, and the leakage point of the refrigerant may also appear in any part of the refrigeration system.

1, evaporator leak

Common air conditioning refrigerant leakage several major parts and treatment methods

There are many welds on the left and right sides of the evaporator, and there may be more leaks. The newly installed air conditioner leaks mainly because the welding technology of the air conditioner manufacturer is not good. When the copper tube is not burnt red (the temperature does not reach 600 ° C ~ 700 ° C), the electrode is placed at the weld, the copper tube and The solder is not fused together, causing the weld to be pinched, slag, and not smooth, resulting in leakage of the refrigerant.

Operation: Remove the electrical box on the right side of the indoor unit, remove the fixed line and splint on the rear side of the evaporator, and remove the left and right positioning screws of the indoor evaporator. After pulling the evaporator out 5 cm, the evaporator was rotated 90 degrees with both hands and pulled out along the pipe. After the evaporator is removed. Put it in a clean, clean place and wipe off the leaking oil with a dry cloth. The leak point is welded by silver welding.

2. Leakage at the indoor unit connection

Common air conditioning refrigerant leakage several major parts and treatment methods

The air conditioner is operating normally, and the indoor unit is not blown out by air, considering whether the refrigeration system is faulty. If there is oil trace at the connection of the indoor unit, the refrigerant leaks here.

Operation: Apply with a bubble of water and check for bubbles at the joint. If not, the refrigerant can be added from the low pressure gas valve bypass nozzle, which is based on a low pressure of 0.5 MPa. Stop using the washing spirit and check the nano-spot. After 3 to 5 minutes, there is still no bubble generation, indicating that the leak at the joint is faulty.

refrigerant copper pipe

3, outdoor machine stop valve leakage

Common air conditioning refrigerant leakage several major parts and treatment methods

Most of the outdoor machine cut-off valve core leakage occurs after the transfer machine. Because the switch valve shaft is screwed in and out, and the rubber ring is aged for a long time, the outer shaft sealing rubber ring is worn out, causing the shut-off valve to leak. If the leak is serious, you can hear the sound of “zz…”, and the refrigerant can be discharged from the low-pressure gas locker of the outdoor unit.

Operation: Use a hex wrench to unscrew the shut-off valve screw, and block the leaking position with your left hand. The right hand quickly winds the 4 turns of the raw material belt at the screw and seal ring of the screw, and quickly turns the shut-off valve screw to the good snap ring. Then, 2-3 turns of the raw material tape on the secondary sealing thread, and the secondary sealing cap is placed. Add F22 refrigerant from the low-pressure gas cut-off bypass valve, and add F22 gas to about 0.5MPa (for reference).

4, outdoor compressor U-tube leakage

Common air conditioning refrigerant leakage several major parts and treatment methods

The leakage of U-type exhaust pipe of outdoor compressor is more common. The main reason is that the copper pipe has a thin wall and poor material. After bending into a U-bend, small cracks appear. The vibration generated by the compressor during work increases the crack. . Most of this leakage failure will leak the refrigerant.

5, outdoor machine capillary vibration wear and tear

Common air conditioning refrigerant leakage several major parts and treatment methods

The reason for the leakage of the refrigerant may also be the vibration generated when the compressor works, causing the two tubes to resonate and rub, and the wall of the tube is worn out to cause the refrigerant to leak light.

Example: A XX split type air conditioner is not cooled, and it is found that the capillary leaks. The method of elimination is to saw a 6mm copper tube with a saw, wrap it around the capillary leak, and then weld it with silver. It is also possible to replace capillaries of the same diameter and the same size. Before replacing the welding, there shall be no flammable or explosive materials within 1.5m. There should be an iron plate behind the capillary. When welding, the flame should not be too large, and the neutral flame should be used. The temperature reaches 600 °C, and the silver electrode is quickly placed on the weld. The solder and the copper tube melt together and the torch quickly leaves, otherwise the capillary will be blown.

6, low pressure bypass spool leakage

Common air conditioning refrigerant leakage several major parts and treatment methods

The split type air conditioner refrigeration system is supplemented with refrigerant (commonly known as "fluorine") and must be filled from the low pressure bypass. The ventilating tube with a thimble is used to open the low-pressure gas-filling valve stem, and the R22 refrigerant gas of the refrigerant cylinder and the gas of the air-conditioner refrigerant are connected, and the filling can be performed.

The cause of the malfunction: the ejector pin of the air supply pipe is adjusted too long, and the venting pin of the bypass venting valve cannot be rebounded after being pushed in, so that the valve core cannot be reset. The method of elimination is to insert the key of the special air conditioner into the air-filling valve core, and give the valve core a force to make the valve core spring pop out, thereby eliminating the valve core leakage fault.

7, compressor terminal leakage

Common air conditioning refrigerant leakage several major parts and treatment methods

The compressor terminal leaks, accounting for more than 2% of the leakage fault. Remove the overheating protector cover. If there is oil trace around the compressor terminal, there is a leak.

Operation: Prepare with C31 double tube glue in a 1:1 ratio and apply it at the wiring. Because the refrigeration system is in a vacuum state, the C31 glue penetrates into the leak point. After the leak point is glued, it needs to be baked at the glue for 30 minutes with the 100W bulb, so that the glue can penetrate into the leak point more easily. Note that the bulb should not be too close to the C31 glue. It is better to use C31 glue 20cm. Otherwise, the glue will be baked and flow to the compressor, which will reduce the plugging effect. After the compressor terminal is glued for 2 hours, it can be pressed and leak tested. Finally, evacuate and add a fluorine test machine to restore refrigeration.

8, the pipeline is leaking

Common air conditioning refrigerant leakage several major parts and treatment methods

The leaks in the pipelines often appear after the renovation of the home. Some decoration workers do not understand the refrigerant in the refrigeration pipeline; if they are bent, because there is a thermal insulation sleeve outside the pipeline, it is not easy to be found after bending. After the pipe is recessed, the refrigerant will leak, and even if the fluorine is re-fluorinated, the refrigeration system will have two interception symptoms.

Operation: Remove the concavity interception with a cutter, use the outer casing to dock, after welding with silver, re-press, leak, evacuate, add fluoride, start with remote control

9, four-way reversing valve leakage

Common air conditioning refrigerant leakage several major parts and treatment methods

There are more leaks in the corners of the three copper pipes under the four-way valve of the cold and warm air conditioner. If there is oil trace at the corner, it indicates that there is a leak.

Operation: Discharge the refrigerant and wrap the four-way reversing valve with a wet towel. When welding, you should master the flame technology according to your own, align the leak point, and when the angle reaches the welding temperature, quickly solder the silver electrode.